Permit Review Detail
Review Status: Completed
Review Details: SITE
Permit Number - T07CM02117
Review Name: SITE
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/10/2007 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 08/14/2007 | TERRY STEVENS | ZONING | REVIEW | Denied | 08/17/07 Development Services Department Zoning Review Section Terry Stevens Lead Planner Comments: 1. The Cell Tower site plan and building plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Special Exception section and Structural section of DSD. 2. Condition #4 of the special exception conditions requires the monopole to be painted to match the surrounding light poles. Indicate on plans. 3. Condition #2 of the special exception conditions requires the monopole to be a maximum of 40' above grade. The structural plan, done by EEI, indicates that the monopole will be 41' or more above grade. Revise to comply with condition. |
| 08/17/2007 | TERRY STEVENS | ZONING HC SITE | REVIEW | Passed | |
| 08/23/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | |
| 08/29/2007 | PETER MCLAUGHLIN | LANDSCAPE | REVIEW | Approved | |
| 08/29/2007 | PETER MCLAUGHLIN | NPPO | REVIEW | Approved | |
| 09/12/2007 | PATRICIA GILBERT | ENGINEERING | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 09/14/2007 | VFLORES1 | OUT TO CUSTOMER | Completed |
| 09/14/2007 | VFLORES1 | REJECT SHELF | Completed |