Permit Number: T07CM02031
Parcel: 141185830

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T07CM02031
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/15/2007 TERRY STEVENS ZONING REVIEW Approved
05/16/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
05/16/2007 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
05/16/2007 ROBERT SHERRY WATER REVIEW Approved
05/16/2007 CHRIS KIEL (WILDAN) BUILDING-COMMERCIAL REVIEW Denied 1. PLEASE PROVIDE A DRINKING FOUNTAIN IN ACCORDANCE WITH TABLE 2902.1 OF THE 2003 IBC. BOTTLED WATER COOLERS ARE PERMITTED TO REPLACE NOT MORE THAN 50% OF THE REQUIRED DRINKING FOUNTAINS.

2. PLEASE PROVIDE ADDITIONAL INFORMATION REGARDING THE CEILING FRAMING ABOVE THE RESTROOM THAT SUPPORTS THE WATER HEATER PER SECTION 106.1.1 OF THE 2003 IBC.
05/16/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
05/16/2007 DAVE MANN FIRE REVIEW Approved
05/24/2007 CAGUILA1 WWM REVIEW Needs Review
05/24/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
05/24/2007 CAGUILA1 ENGINEERING REVIEW Needs Review