Permit Number: T07CM01993
Parcel: 12417157A

Address:
1050 E 19TH ST

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T07CM01993
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/16/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T07CM01993 11/16/07

Lumens for the fixtures on the Lighting Code Compliance schedule do not correspond to appropriate lumen counts for wattages involved. Without identification of lighting source it is not possible to perform further evaluation. Additionally, identification of lighting source for each fixture type would be necessary to evaluate per Option 1 of Table 5.1. However, it appears upon inspection that the lighting added is less than 10% of the total. Suggest that Section 8.1 Paragraph 4 be cited in lieu of this table.