Permit Number: T07CM01993
Parcel: 12417157A

Address:
1050 E 19TH ST

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T07CM01993
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/09/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
10/09/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
10/09/2007 ROBERT SHERRY WATER REVIEW Approved
10/18/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T07CM01993 10/18/07

1. Exterior lighting fixture shall be wet listed.
2. Demonstrate compliance with the 2006 IECC. This comment was made on the 10/9/07 review. Provide calculations to verify compliance with Interior Lighting Power Allowances of Table 505.5.2.
3. Demonstrate compliance with the Tucson Lighting Code. This comment was made on the 10/9/07 review.
4. Provide service load calculations. This comment was made on the 10/9/07 review. Kilowatt hour is not a basis for demand readings. A 1998 number would be too dated to accept in any case.
5. Please provide the conductor sizing for the new feeder.