Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T07CM01993
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/09/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
10/09/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
10/09/2007 | ROBERT SHERRY | WATER | REVIEW | Approved | |
10/18/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T07CM01993 10/18/07 1. Exterior lighting fixture shall be wet listed. 2. Demonstrate compliance with the 2006 IECC. This comment was made on the 10/9/07 review. Provide calculations to verify compliance with Interior Lighting Power Allowances of Table 505.5.2. 3. Demonstrate compliance with the Tucson Lighting Code. This comment was made on the 10/9/07 review. 4. Provide service load calculations. This comment was made on the 10/9/07 review. Kilowatt hour is not a basis for demand readings. A 1998 number would be too dated to accept in any case. 5. Please provide the conductor sizing for the new feeder. |