Permit Number: T07CM01993
Parcel: 12417157A

Address:
1050 E 19TH ST

Review Status: Completed

Review Details: OTHER

Permit Number - T07CM01993
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/09/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T07CM01993 10/9/07

1. Remove all references to the IRC. City enforces the 2005 National Electrical Code, and its local amendments.
2. Electrical Note 4 refers to a garage. Not in this project.
3. Electrical Note 5 refers to a rooms not in this project.
4. Provide lighting fixture schedule.
5. Demonstrate compliance with the 2006 IECC.
6. Provide lighting cut sheets.
7. New receptacle circuits, at 180VA per receptacle, would be 900VA, not 720.
8. Add 25% for lighting/continuous load, on panel schedule.
9. VA per phase, at 23 MCA, would be 2760, not 1600.
10. Demonstrate compliance with the Tucson Lighting Code.
11. Provide service load calculations.
10/09/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
10/09/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved