Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T07CM01993
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/09/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T07CM01993 10/9/07 1. Remove all references to the IRC. City enforces the 2005 National Electrical Code, and its local amendments. 2. Electrical Note 4 refers to a garage. Not in this project. 3. Electrical Note 5 refers to a rooms not in this project. 4. Provide lighting fixture schedule. 5. Demonstrate compliance with the 2006 IECC. 6. Provide lighting cut sheets. 7. New receptacle circuits, at 180VA per receptacle, would be 900VA, not 720. 8. Add 25% for lighting/continuous load, on panel schedule. 9. VA per phase, at 23 MCA, would be 2760, not 1600. 10. Demonstrate compliance with the Tucson Lighting Code. 11. Provide service load calculations. |
| 10/09/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 10/09/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved |