Review Date Reviewer's Name Type of Review Description Status Comments
05/14/2007 DAVE MANN FIRE REVIEW Approved Sheet 2 shows a masonry wall for a 1 hour separation. Without a rated door between storage area and business area, no separation exists. Provide fire rated door.
05/22/2007 STEVE SHIELDS ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: SteelDor of Tucson
T07CM01993
Building Plan (1st Review)

TRANSMITTAL DATE: May 22, 2007

1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and Landscape Review Sections and until all zoning comments or concerns have been addressed.

2. Zoning could not verify that the building plan was in compliance with the approved site plan. Please submit two copies of the approved and stamped site, landscape, and NPPO plans with the next building plan submittal.

3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved and stamped site plan. Additional comments may be forthcoming.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956.

C:\planning\grading\t07cm01666.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised site plan and additional requested documents
05/22/2007 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Denied 1) PLEASE REVISE CODE ANALYSIS TO REFLECT IBC DESIGNATOR "VB" AS TYPE OF CONSTRUCTION.

2) PLEASE USE 2003 IBC SECTION 506 EQUATIONS 5-1 AND 5-2 TO CORRECTLY CALCULATE ALLOWABLE AREA.

3) 2 HOUR FIRE RESISTANCE BETWEEN THE B AND F2/S2 OCCUPANCIES IS REQUIRED PER 2003 IBC TABLE302.3.2.

4) A 2 HOUR FIRE BARRIER REQUIRES A 90 MINUTE FIRE RATED DOOR PER TABLE 715.3 OF THE 2003 IBC.
06/14/2007 SUE REEVES COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
06/18/2007 GERARDO BONILLA OUT TO CUSTOMER Completed
06/18/2007 GERARDO BONILLA REJECT SHELF Completed