Permit Number: T07CM01988
Parcel: 13325183B

Review Status: Completed

Review Details: POST 3RD PARTY REVIEW

Permit Number - T07CM01988
Review Name: POST 3RD PARTY REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/06/2007 ROBERT SHERRY WATER REVIEW Denied Provide a letter from Tucson Water confirming that the use of a 1-1/2" water meter will be allowed for this project (152 fixture units equates to a demand of 55 GPM)
11/06/2007 DAVE MANN FIRE REVIEW Denied Incorrect design criteria for sprinkler system on sheet P 1.
If these shops are to be used for retail sales, the hazard classification should Ordinary Group II, with a density of 0.20 over 1500 sq. ft.
Also, please include flow data (static pressure, residual pressure, and GPM). This data is available from the Systems Engineering section of the fire department. The number is 791-3234.
11/07/2007 TERRY STEVENS ZONING REVIEW Denied 11/07/07

Development Services Department
Zoning Review Section

Terry Stevens
Lead Planner

Comments:

1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and Landscape Review Sections and until all zoning comments or concerns have been addressed.

2. Zoning could not verify that the building plan was in compliance with the approved site plan. Please submit two copies of the approved and stamped site, landscape, and NPPO plans with the next building plan submittal.

3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved site plan. Additional comments may be forthcoming.
11/13/2007 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed Impact Fee's Do Apply; East District; 1,000 Square Feet of Retail; $2,038; This permit is a full build out and occupancy of space has been determined. However with no established tenant, a letter of completion will be issued.
11/13/2007 PATRICIA GILBERT ENGINEERING REVIEW Denied Submit the approved site plan with the building plan.
11/15/2007 GERRY KOZIOL WWM REVIEW Denied NEEDS 8TH FLOOR REVIEW & APPROVAL
MANHOLE TAP PERMIT (AGAINST FLOW)
CLEAN OUT IN R.O.W.

Final Status

Task End Date Reviewer's Name Type of Review Description
12/04/2007 GERARDO BONILLA OUT TO CUSTOMER Completed
12/04/2007 GERARDO BONILLA REJECT SHELF Completed