07/27/2007 JASON GREEN ENGINEERING REVIEW Approved DATE: July 27, 2007
SUBJECT: 5023 E 29th St- Tenant Improvement to an existing Barbershop
TO: Wayne Swan
LOCATION: T14S R14E Sec23, Ward 5
REVIEWERS: Jason Green, CFM
ACTIVITY: T07CM01962 (Site Plan) and T07OT01718 (Floodplain Use Permit)


SUMMARY: Engineering Division of Development Services Department has received and reviewed the Site Plan (T07CM01962), Floodplain Use Permit (T07OT01718), and the submitted cost estimate for the proposed tenant improvements for the above referenced property. Engineering Division recommends approval of the Site Plan and Floodplain Use Permit at this time.
CONDITIONS OF PERMIT:

1) The associated improvements are with permit activity number T07OT01718 (Floodplain Use Permit) and T07CM01962 (building plans).
2) Any improvements to the structural building for this project are considered a substantial improvement to an existing floodprone structure if the value of this new improvement is 50% or more than the value of the existing structure in present day value. If the project is determined to be a substantial improvement, and, if it is determined that the lowest floor elevation is below the regulatory floor elevation, a design submittal, and review and acceptance of the submittal for flood proofing will be required and shall conform to City of Tucson floodplain development requirements.
3) Cumulative values shall be accounted for the building structure, so that tracking of the 50% status is current. No person shall repair or alter property in a piecemeal manner so as to avoid the provisions of Section 26-4.1.a.3, Chapter 26-Floodplain and Erosion Hazard Management.
4) The applicant attests to the fact that the plans and documents submitted represent all of the improvements that will be done to the existing building, and that all additions, improvements or repairs to the building are included in the construction plans and/or documents herewith. No other improvements, repairs, reconstruction, additions or remodeling have been made to the structure that is not indicated in the attached plans and/or documents.
5) This permit is specific to the improvements specified as the tenant improvement to an existing barbershop as shown on this plan. It shall not apply to any other structure or property, whether attached or unattached, not specified under this permit.
6) Copies of the improvement plans/permit documents shall be kept in a readily accessible location on site at all times.


If you have any questions, I can be reached at 837-4929.



Jason Green, CFM
Senior Engineer Associate
Engineering Division
Development Services

Final Status

Task End Date Reviewer's Name Type of Review Description
07/31/2007 THAUSER1 OUT TO CUSTOMER Completed