Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T07CM01962
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/12/2007 | CHRIS KIEL (WILDAN) | BUILDING-COMMERCIAL | REVIEW | Denied | 1) Please provide at least one accessible sink per section 1109.3 of the 2006 IBC and section 606 of ANSI 117.1-2003 (i.e. maximum 34" height and pipe protection). |
| 07/12/2007 | VFLORES1 | WWM | REVIEW | Needs Review | |
| 07/12/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Revise the water fixture units per Table 6-5, UPC 2006. 2. How is the water service provided to the sinks? Reference Section 103.2.3, UPC 2006. |
| 07/12/2007 | JASON GREEN | ENGINEERING | REVIEW | Needs Review | |
| 07/12/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 07/12/2007 | ROBERT SHERRY | WATER | REVIEW | Denied | Comment not addressed. How is the water supplied to this space; individual meter or common water supply? |
| 07/12/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed |