Permit Number: T07CM01961
Parcel: 137051610

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T07CM01961
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/30/2009 DAVE MANN FIRE REVIEW Approved
12/03/2009 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
12/03/2009 RONALD BROWN ZONING HC REVIEW Denied 1. The accessible water fountain is not compliant with 2006 IBC, Chapeter 11, Section 1109.5 and ICC (ANSI) 117.1, Section 602.4, dual height spouts, or provide a "Point of Use" water dispenser.
12/04/2009 STEVE SHIELDS ZONING REVIEW Approved
12/11/2009 GERRY KOZIOL WWM REVIEW Approved
12/11/2009 LOREN MAKUS ENGINEERING REVIEW Approved
12/16/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide additional cleanouts in drainage pipe for each aggregate horizontal change of direction exceeding 135 degrees and sized per Table 7-6, UPC 2006. Reference Sections 707.5 and 707.11, UPC 2006.
2. A service sink requires a minimum trap and trap arm size of 2". Reference: Table 7-3, UPC 2006.
3. The specified drinking fountain does not meet the accessibility requirements as shown in Section 1109.5, IBC 2006.
12/16/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
12/16/2009 ROBERT SHERRY WATER REVIEW Passed
12/17/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
02/08/2010 CPIERCE1 OUT TO CUSTOMER Completed
02/08/2010 SUE REEVES REJECT SHELF Completed