Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL - SITE ALL
Permit Number - T07CM01961
Review Name: RESUBMITTAL - SITE ALL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/30/2009 | DAVE MANN | FIRE | REVIEW | Approved | |
| 12/03/2009 | RONALD BROWN | ZONING HC | REVIEW | Denied | 1. At note "H": Please include flared sides on concrete entrance as required by ICC (ANSI) 117.1, Section 303.3. 2. The farthest West detectable warning is not required. It is not part of a marked crossing and does not lead to a hazardous area. Please remove. 3. Please clarify the elevation of the new concrete accessible route to the vehicle paving by providing a section detail of same. 4. Please provide an accessible parking signage detail including a "Van Accessible" sign. END OF REVIEW |
| 12/04/2009 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 12/08/2009 | ANDREW CONNOR | NPPO | REVIEW | Approved | |
| 12/08/2009 | ANDREW CONNOR | LANDSCAPE | REVIEW | Approved | |
| 12/11/2009 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 12/16/2009 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 02/03/2010 | SUE REEVES | OUT TO CUSTOMER | Completed |
| 02/03/2010 | CPIERCE1 | REJECT SHELF | Completed |