Permit Number: T07CM01961
Parcel: 137051610

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T07CM01961
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/16/2007 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. CHANGE TO ADA APPROVED EWC FROM WATER DISPENSER WAS APPROVED, HOWEVER ELKAY MODEL EBFSA-4G IS A SINGLE HEIGHT EWC. ANSI 117.1.1, SECTION 602.4 REQUIRES TWO SPOUT HEIGHTS AND SECTION 306 CALLS FOR 30" WIDTH CLEARANCE FOR EACH UNIT.
11/27/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide additional cleanouts in drainage pipe for each aggregate horizontal change of direction exceeding 135 degrees and sized per Table 7-6, UPC 2006. Reference Sections 707.5 and 707.11, UPC 2006.
2. A service sink requires a minimum trap and trap arm size of 2". Reference Table 7-3, UPC 2006.
11/28/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
12/03/2007 STEVE SHIELDS ZONING REVIEW Approved
12/14/2007 GERRY KOZIOL WWM REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
12/18/2007 GERARDO BONILLA OUT TO CUSTOMER Completed
12/18/2007 GERARDO BONILLA REJECT SHELF Completed