Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T07CM01961
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/16/2007 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | 1. CHANGE TO ADA APPROVED EWC FROM WATER DISPENSER WAS APPROVED, HOWEVER ELKAY MODEL EBFSA-4G IS A SINGLE HEIGHT EWC. ANSI 117.1.1, SECTION 602.4 REQUIRES TWO SPOUT HEIGHTS AND SECTION 306 CALLS FOR 30" WIDTH CLEARANCE FOR EACH UNIT. |
| 11/27/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide additional cleanouts in drainage pipe for each aggregate horizontal change of direction exceeding 135 degrees and sized per Table 7-6, UPC 2006. Reference Sections 707.5 and 707.11, UPC 2006. 2. A service sink requires a minimum trap and trap arm size of 2". Reference Table 7-3, UPC 2006. |
| 11/28/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 12/03/2007 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 12/14/2007 | GERRY KOZIOL | WWM | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 12/18/2007 | GERARDO BONILLA | OUT TO CUSTOMER | Completed |
| 12/18/2007 | GERARDO BONILLA | REJECT SHELF | Completed |