Review Details: COMMERCIAL TI

Permit Number - T07CM01961
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/21/2007 MARTIN BROWN FIRE REVIEW Approved
05/22/2007 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Denied 1) SUBMIT PLANS WITH DETAILS AND COMMENTS WITH MINIMUM 1/8" FONT.

2) PROVIDE DETECTABLE WARNING TO PARKING LOT PER ANSI 117.1 SECTION 406.12

3) DETAIL ACCESSIBILITY FOR SINK IN BREAKROOM. REF IBC 1109.3

4) PROVIDE APPROVED APPEAL FROM BUILDING OFFICIAL TO SUBSTITUTE BREAKROOM SINK + BOTTLED WATER FOR REQUIRED DRINKING FOUNTAIN.
05/24/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide calculations demonstrating adequate ventilation. Reference Section 401.2, IMC 2003.
2. Ventilation for restrooms in public spaces requires a minimum of 75 CFM of mechanical exhaust per water closet or urinal. Reference Table 403.3, IMC 2003.
3. Show that the building is capable of maintaining a minimum temperature of 68°F in the interior spaces intended for occupancy on a design heating day (32°F). Reference Sections 309.1 and 312.1, IMC 2003.
05/24/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference Section 302.3, Uniform Administrative Code, 1997.
2. Revise the site drawing to show the size and route of the building water supply from the water meter to the building shut off valve. Reference Section 103.2.3, UPC 2003.
3. Revise the site drawing to show the route of the building sewer from the building to the connection with the public sewer. Indicate the locations of all of the cleanouts and extend them to grade. Reference Sections 103.2.3 and 719.0, UPC 2003.
4. Provide plumbing plans for the new work, including water isometrics. Reference Section 103.2.3, UPC 2003.
5. Coordinate the plumbing plans and riser diagrams (e.g. show the existing service sink on the waste & vent diagram). Reference Section 103.2.3, UPC 2003.
6. Provide the minimum plumbing facilities required by Table 2902.1, IBC 2003, for business occupancy (e.g. drinking fountain). Substitution of a bottled water dispenser for a drinking fountain will require an appeal to the building official prior to approval of the plumbing plans. Reference Section 301.2, UPC 2003.
7. Show the size of the trap and trap arm for the existing service sink. Reference Section 103.2.3, UPC 2003.
8. Show that the relocated water closet complies with Section 409.0, UPC 2003.
9. Provide vent piping of sufficient size to comply with Section 904.1, UPC 2003.
05/24/2007 ROBERT SHERRY WATER REVIEW Passed
05/29/2007 STEVE SHIELDS ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: ABC Insurance
T07CM01961
Building Plan (1st Review)

TRANSMITTAL DATE: May 30, 2007

1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and Landscape Review Sections and until all zoning comments or concerns have been addressed.

2. Zoning could not verify that the building plan was in compliance with the approved site plan. Please submit two copies of the approved and stamped site, landscape, and NPPO plans with the next building plan submittal.

3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved and stamped site plan. Additional comments may be forthcoming.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956.

C:\planning\grading\t07cm01961.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised site plan and additional requested documents
05/29/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov
IF YOU CARE TO DISCUSS.

1. Code Analysis on Sheet A1 refers to Lighting Plan for exit signs. No such lighting plan.
2. Provide electrical load calculations and line diagram.
3. Provide electrical plans for any work performed after the last permitted occupancy.
06/18/2007 GERRY KOZIOL WWM REVIEW Denied NEEDS 8TH FLOOR CREDIT EVALUATION

Final Status

Task End Date Reviewer's Name Type of Review Description
06/27/2007 GERARDO BONILLA OUT TO CUSTOMER Completed
06/27/2007 SUE REEVES REJECT SHELF Completed