Permit Number: T07CM01923
Parcel: 112010650

Address:
2708 E CLAYS AL

Review Status: Completed

Review Details: RESIDENTIAL BLDG/ZONING/ENGINE/WWM

Permit Number - T07CM01923
Review Name: RESIDENTIAL BLDG/ZONING/ENGINE/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/24/2007 THAUSER1 LANDFILL REVIEW Passed
06/12/2007 BUREAU VERITAS 2ND PARTY REVIEW REVIEW Denied June 8, 2007 CITY OF TUCSON - FIRST CHECK
Tucson Appl. No. T07CM01923
Bureau Veritas Job No. 01007-161001.051

Mr. Mark Bathi
4280 N. Campbell #100
Tucson, Arizona 85718


Re: Plan Review: Bahti SFR
Address: 2708 E. Clay’s Alley


Dear Mr. Bahti:

Bureau Veritas North America has completed a first review of the following documents on behalf of the City of Tucson:

Plans: Two (2) sets of building plans (10 sheets, T1 through E1.0) no dates, no stamps.

Structural Calculations: None submitted with this review.

Truss Calculations: None submitted with this review.




These documents were reviewed only for their conformance to the provisions of the 2006 International Building Codes (i.e., State of Arizona and Tucson amended 2006 IRC)

Please submit an itemized response letter and required number of complete and revised documents with all revisions clouded.


Sincerely,

Bureau Veritas North America



Shelley Knuffke
ICC Plans Examiner










SK:sk

Re: Stories: One
Occupancy: R-3/VB
Building Area (sq. ft.): 1698 (livable)
124 (porch)
1822 Total sq. ft.


A. The following plan review comments are based on the City of Tucson Building Regulations and referred to the 2006 International Building Code.

B. Please respond in writing to each comment by marking the attached comment list or creating a response letter. Indicate which detail, specification, or calculation shows the requested information. Your complete and clear responses will expedite the re-check and hopefully, approval of this project. Thank you for your assistance.

C. These plan review comments are based on building code items only. If site-related comments are applicable to this project, they will be generated by others (e.g., County Engineering, Public Works, Health, etc.).

GENERAL REQUIREMENTS:

You must petition the Building Official by letter to approve the use of the 2006 IRC, as the City of Tucson is currently in the 2003 codes.

Provide an accurate index to drawings on the first sheet of the set.

Provide specifications with manufacturers installation information on the AAU/AAC
E-Crete jumbo block. P

FLOOR PLAN COMMENTS:

Label all rooms and spaces, show all doors. Locate and identify heights of all ceilings. Include hallways, utility rooms, garages and walk-in closets.

Note and specify that the shower area walls shall be finished with a nonabsorbent surface to a height of six feet above the floor.

Locate skylights. Notes indicate use of skylights however they are not located on the plan.

Every sleeping room and basement with habitable space shall have at least one window minimum net clear opening 5.7 square feet (minimum 5 square feet net clear opening at grade floor), minimum opening width of 20 inches, minimum opening height of 24 inches and the finished sill height shall not be more than 44 inches above the floor; or provide exterior door for emergency egress. IRC Section R310.1.

Appliances having an ignition source shall be elevated such that the source of ignition is not less than 18 inches above the floor in garages. For the purpose of this section, rooms or spaces that are not part of the living space of a dwelling unit and that communicate with a private garage through openings shall be considered to be part of the garage. Floor plan calls out a 16” platform. Clarify.




ELEVATIONS:

Indicate all materials used – Provide information and specs for metal roof.

For thin coat stucco systems over foam board, note and specify the ICC Evaluation Report number, system name and manufacturer. Note and specify the vapor barrier used.

ROOF PLAN COMMENTS:

Note and specify a complete roofing system: Specify roofing type, grade of materials, valley flashing material, underlayment required and method of installation, attachments of roofing materials as required.

Provide attic ventilations calculations of all concealed attic spaces; include required and provided net free ventilation area. Also indicate the type and location of attic ventilation. Provide the following note, if applicable: “Where eave or cornice vents are installed insulation shall not block the free flow of air. A minimum of 1 inch space shall be provided between the insulation and roof sheathing at the location of the vent”.

FOUNDATION PLAN:

Show details for crawlspace. Proper distance between floor framing members and the earth.

Footing details (interior and exterior) shall be located on the foundation sheet or the detail sheet and shall be cross-referenced to the foundation plans. Specify depth and size of all footings and pads.

Locate and specify all anchor bolt spacing and post anchors on the foundation.

Show location of underground return air ductwork on the foundation plan (fireplace venting?)

FRAMING PLAN COMMENTS:

Note on the plan all lumber shall bear an approved grading stamp.

Provide Header/lintel schedule.

Specify design criteria: floor and roof live and dead loads. IRC Section R301.

Indicate the size and span of all headers and lintels in all bearing and non-bearing walls. Provide manufacturer’s span charts for pre-manufactured steel lintels.

Detail and specify anchorage for all trusses and framing members.


TRUSS SYSTEMS: Trusses can be submitted as a “Deferred Submittal”. However, they must be submitted and approved prior to their fabrication.





MECHANICAL PLAN COMMENTS:

1. Provide combustion air for all liquid and solid fuel-burning appliances including size, type and location of openings. IRC Section M1501.1.


PLUMBING COMMENTS:

Provide a gas isometric to clearly convey design including length of line (horizontal and vertical) to each appliance, BTU demand of each appliance, size of each branch, total demand and size of the meter.

Note that drainage piping serving fixtures which have flood level rims located below the elevation of the next upstream manhole cover of the public sewer shall be protected from backflow of sewage by a backwater valve. IRC Section P3008.

Specify materials for waste, water and gas pipes.

Provide a drainage pipe isometric showing all drain waste and vent piping.




If you have any questions regarding the above comments, please contact Shelley Knuffke at (520) 576-8400 between 8:00 A.M. to 5:00 P.M., M-F.
06/13/2007 SEPTIC APPROVAL WWM REVIEW Denied need septic design & review fee

Final Status

Task End Date Reviewer's Name Type of Review Description
07/05/2007 VFLORES1 OUT TO CUSTOMER Completed
07/05/2007 VFLORES1 REJECT SHELF Completed