Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Permit Number - T07CM01913
Review Name: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/14/2007 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | 1. SES GEAR SHOWS A 175A DISCONNECT WITH 4#2'S, CONDUCTORS, TOO SMALL. 2. SHEET E-2 #6 INDICATES 175A DISCONNECT NOT TO BE USED? 3. SHEET E-4 DETAIL A #1,NEW 2-P 30A DISCONNECT FUSED AT 200A? 4. SHEET E-4 DETAIL A SHOWS A #12AWG GROUND TO GROUND ROD, TOO SMALL. 5. SHEET E-4 DETAIL B SHOWS A # 10 AWG GROUND TO GROUND ROD, TOO SMALL. 6. SHEET E-4 DETAIL C STATES COIL VOLTAGE 120V,PLAN SHOWS CONNECTION TO 277V CIRCUIT,ALSO PHOTO-ELECTRIC CELL AT 120V CONNECTED TO 277V CIRCUIT. 7. SHEET E-4 DETAIL 8 SHOWS PEDISTAL TO BE FROM SES SW GEAR, HOWEVER IT APPEARS TO BE FED FROM PNL GP IN SB1 NOT SES. |
| 05/21/2007 | CHRIS KIEL (WILDAN) | BUILDING-COMMERCIAL | REVIEW | Denied | 1) PLEASE SPECIFY THE WALL THICKNESS ASSOCIATED WITH THE 8" METAL POLE IN ASSOCIATION WITH THE STRUCTURAL CALCULATIONS PER SECTION 106.1.1 OF THE 2003 IBC (SCHEDULE 40). 2) PLEASE SPECIFY THE MAXIMUM HEIGHT OF THE SCOREBOARD IN ASSOCIATION WITH THE STRUCTURAL CALCULATIONS PER SECTION 106.1.1 OF THE 2003 IBC. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 06/22/2007 | VFLORES1 | OUT TO CUSTOMER | Completed |
| 06/22/2007 | SUE REEVES | REJECT SHELF | Completed |