Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T07CM01895
Parcel: 105110690

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T07CM01895
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/30/2007 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Denied 1. Provide drinking fountain per table 2902.1 of the 2003 IBC. Ref: previous correction comment #6 "PLEASE PROVIDE ADDITIONAL INFORMATION FOR THE DRINKING FOUNTAIN IN ORDER TO VERIFY COMPLIANCE WITH SECTION 602 OF ANSI 117.1-2003. PLEASE ENSURE THAT THE DRINKING FOUNTAIN ALSO COMPLIES WITH SECTIONS 307 OF ANSI 117.1-2003 AND 1003.3.3 OF THE 2003 IBC."

2. While the shell drawings confirm that you may use non-seperated use for this TI please put allowable area code analysis information on your plan. Reference previous correction comment #9.
08/03/2007 ROBERT SHERRY WATER REVIEW Approved
08/03/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide the minimum plumbing facilities required by Table 2902.1, IBC 2003, for business occupancy (e.g. a drinking fountain).
2. The specified instantaneous water heaters (Eemax SP8208, 208V, single phase, 8.3 kW) are listed for use with dual faucets (SP refers to "top water connections", not "single point"), and do not have the ability to be factory set for a maximum outlet temperature.
08/03/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference Section 302.3, Uniform Administrative Code, 1997.
2. Provide a smoke detector in the return air duct, upstream of any outside air connections, for all air distribution systems with a capacity greater than 2,000 CFM. Reference Section 606.1, IMC 2003.

Final Status

Task End Date Reviewer's Name Type of Review Description
08/06/2007 DELMA ROBEY APPROVAL SHELF Completed
08/06/2007 DELMA ROBEY OUT TO CUSTOMER Completed
08/06/2007 GERARDO BONILLA REJECT SHELF Completed