Permit Number: T07CM01895
Parcel: 105110690

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T07CM01895
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/07/2007 DAVE MANN FIRE REVIEW Approved
05/10/2007 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
05/15/2007 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
05/18/2007 CHRIS KIEL (WILDAN) BUILDING-COMMERCIAL REVIEW Denied 1) PLEASE REVISE THE LISTED CODES TO THOSE ADOPTED BY THE CITY OF TUCSON PER SECTION 106.1.1 OF THE 2003 IBC (i.e. 2003 IBC, IMC, IECC, 2002 NEC, 2003 UPC).

2) PLEASE REVISE THE TOILET ROOMS TO PROVIDE THE REQUIRED CLEARANCE AT THE WATER CLOSETPER SECTION 604.3.2 OF ANSI 117.1-2003.

3) PLEASE PROVIDE THE REQUIRED VERTICAL GRAB BAR PER SECTION 604.5.1 OF ANSI 117.1-2003.

4) PLEASE REVISE THE TOILET PAPER DISPENSER LOCATION PER SECTION 604.7 OF ANSI 117.1-2003.

5) PLEASE SPECIFY THE KNEE AND TOE CLEARANCES AND PIPE PROTECTION FOR THE LAVATORIES PER SECTIONS 606.2 AND 606.6 OF ANSI 117.1-2003.

6) PLEASE PROVIDE ADDITIONAL INFORMATION FOR THE DRINKING FOUNTAIN IN ORDER TO VERIFY COMPLIANCE WITH SECTION 602 OF ANSI 117.1-2003. PLEASE ENSURE THAT THE DRINKING FOUNTAIN ALSO COMPLIES WITH SECTIONS 307 OF ANSI 117.1-2003 AND 1003.3.3 OF THE 2003 IBC.

7) PLEASE PROVIDE A HARD NONABSORBENT SURFACE ON THE WALLS ADJACENT TO THE WATER CLOSETS PER SECTION 1210.2 OF THE 2003 IBC.

8) PLEASE REVISE THE HEIGHT OF THE BASE IN THE TOILET ROOMS IN ACCORDANCE WITH SECTION 1210.1 OF THE 2003 IBC (MIN 6").

9) PLEASE PROVIDE THE SHELL BUILDING PLANS AND A LISTING OF THE MOST RESTRICTIVE USES WITHIN THE BUILDING IN ACCORDANCE WITH SECTION 106.1.1 OF THE 2003 IBC.

10) PLEASE PROVIDE EGRESS ILLUMINATION WITH EMERGENCY POWER AT THE EXIT DISCHARGE IMMEDIATELY ADJACENT TO THE EXITS PER SECTION 1006.3 OF THE 2003 IBC.

11) PLEASE REVISE THE TEXT SIZE TO A MINIMUM OF 1/8" PER THE CITY OF TUCSON SUBMITTAL REQUIREMENTS AND SECTION 106.1.1 OF THE 2003 IBC.
05/22/2007 ROBERT SHERRY WATER REVIEW Denied Provide a copy of the building shell drawings for evaluation of the water service supply. Reference Section 103.2.3, UPC 2003.
05/22/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference Section 302.3, Uniform Administrative Code, 1997.
2. Coordinate the plumbing notes and diagrams shown on sheet A-4 with the mechanical notes shown on sheets P-1 and P-2. Reference Section 103.2.3, UPC 2003.
3. Provide a copy of the building shell drawings for evaluation of the plumbing system. Reference Section 103.2.3, UPC 2003.
4. Provide upper terminal cleanouts on horizontal drainage pipe over 5 feet in length (e.g. the drinking fountain). Reference Section 707.4, UPC 2003.
05/22/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference Section 302.3, Uniform Administrative Code, 1997.
2. Coordinate the mechanical notes shown on sheet A-2 with the mechanical notes shown on sheets M-1 and M-2. Reference Section 106.3.1, IMC 2003.
3. Provide a programmable thermostat for the rooftop unit per Section 803.2.3.1, IECC 2003 and show the proposed location on the plans.
4. Provide calculations demonstrating adequate ventilation. Reference Section 401.2, IMC 2003.
5. Provide a smoke detector in the return air duct, upstream of any outside air connections, for all air distribution systems with a capacity greater than 2,000 CFM. Reference Section 606.1, IMC 2003.
6. Specify the minimum resistance (R-value) of the duct insulation to be used on this project. Reference Section 803.2.8, IECC 2003.
7. Terminate condensate drains in accordance with Section 307.2.1, IMC 2003, as amended by the City of Tucson.
06/06/2007 GERRY KOZIOL WWM REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
06/15/2007 GERARDO BONILLA OUT TO CUSTOMER Completed
06/15/2007 SUE REEVES REJECT SHELF Completed