Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: POST 3RD PARTY REVIEW
Permit Number - T07CM01890
Review Name: POST 3RD PARTY REVIEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/13/2007 | JOHN WILLIAMS | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 06/13/2007 | DAVE MANN | FIRE | REVIEW | Approved | |
| 06/13/2007 | ROBERT SHERRY | WATER | REVIEW | Denied | 1. Provide backflow protection to isolate the irrigation system from the building water supply. Reference Section 603.4.6.1, UPC 2003. 2. Reduced pressure backflow prevention assemblies shall have a diameter at least equal to the diameter of the service connection or the service line at the point of connection. Reference Section 27-76 (b), COT Ordinance 9976, http://www.tucsonaz.gov/water/docs/backflow-ord.pdf |
| 06/15/2007 | SREEVES1 | WWM | REVIEW | Needs Review | |
| 06/15/2007 | SREEVES1 | ENGINEERING | REVIEW | Needs Review | |
| 06/15/2007 | SREEVES1 | ZONING | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 09/04/2007 | VFLORES1 | OUT TO CUSTOMER | Completed |