Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T07CM01874
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/06/2007 | CAGUILA1 | ZONING | REVIEW | Needs Review | |
| 06/06/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide information on the sequence of operation for the restroom exhaust to show that recirculation of the air from the restroom will not occur. Reference Section 403.2.1, IMC 2003. 2. Provide calculations to show that the common ventilation system is sized in accordance with Section 403.3.2, IMC 2003. |
| 06/06/2007 | JWILLIA5 | ELECTRICAL-COMMERCIAL | REVIEW | Passed | |
| 06/06/2007 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 06/06/2007 | LEERAY HANLY | BUILDING-COMMERCIAL | REVIEW | Denied | 1. PROVIDE CORRECT CODE ANALYSIS FOR ENTIRE BUILDING AND MOST RESTRICTIVE USE IF YOU WANT TO GO NON-SEPERATED USE OR PROVIDE INFORMATION FOR MIXED USE OCCUPANCIES WITH AREA SEPERATIONS. 2. PROVIDE VALUATION |
| 06/06/2007 | RSHERRY1 | WWM | REVIEW | Passed | |
| 06/06/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 06/06/2007 | CAGUILA1 | ENGINEERING | REVIEW | Needs Review | |
| 06/06/2007 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 06/06/2007 | JOHN WILLIAMS | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |