Review Date Reviewer's Name Type of Review Description Status Comments
05/22/2007 DAVE MANN FIRE REVIEW Denied The addition is over 300 feet from the hydrant to the furthest hose lay to to building. Provide another hydrant or automatic fire sprinklers for the building.
05/25/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise the site drawing to include the following information:
a. the location of the main water lines
b. the location and size of the public sanitary sewer and
c. the location, invert, and rim elevation of all manholes and cleanouts.
Reference City of Tucson Development Standard No. 2-05.0 and Section 103.2.3, UPC 2003.
05/31/2007 HEATHER THRALL ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: Night Hawk Trucking - Maintenance Shop & Wash Bay
T07CM01873
Site Plan (1st Review)

TRANSMITTAL DATE: June 4, 2007


COMMENTS: Please resubmit revised drawings and a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and
Development Standards were addressed.

1. This site plan was reviewed for compliance with the City of Tucson Development Standards (D.S.) and Land Use Code (LUC) for full code compliance.

2. All lettering and dimension shall be the equivalent of twelve (0.12") point or greater in size to facilitate reproduction and photographically reduced (microfilm) for record keeping.

3. D.S. 2-02.2.1.A.6 Provide overall dimension for the proposed addition.

4. D.S. 2-02.2.1.A.8 Provide a fully dimensioned parking layout.

5. D.S. 2-02.2.1.A.8 Provide typical parking space details for both handicapped and standard spaces. Provide a detail for the required handicapped signage.

6. D.S. 2-02.2.1.A.8 Based on existing aerial photos and the last approved site plan the areas south of the existing pavement being used for vehicle parking are required to meet LUC Sec 3.3.7.3. The proposed "MILLINGS PAVEMENT" does not meet this requirement.

7. D.S. 2-02.2.1.A.12 It is unclear how the handicapped gain access from the handicapped existing access aisle to the existing sidewalk, clarify.

8. D.S. 2-02.2.1.A.12 Per ICC/ANSI A117.1-2003 Sec. 406 detectable warnings (truncated domes) will be required at all curb access ramps.

9. D.S. 2-02.2.1.A.12 Per D.S. 3-05.2.3.C.1 some type of barrier is required to prevent parking vehicles from overhanging unpaved areas, i.e. the basin located mid property along Renaissance Drive.

10. D.S. 2-02.2.1.A.12 Provide dimensions for all sidewalks, crosswalks and pedestrian refuge areas, existing and proposed, so that compliance with current codes can be verified.

11. D.S. 2-02.A.2.1.13 If applicable provide the location, type, size and height of existing and proposed freestanding signage and billboards.

12. D.S. 2-02.2.1.A.20. Based on the Final Plat there is a 15' electrical easement partially located in the northeast corner of the site. Show on the site plan with recordation information.

13. D.S. 2-02.2.1.A.25 If applicable provide existing and proposed freestanding lighting layout and type. Provide a detail; list the height of pole and type of lighting.

14. D.S. 2-02.2.2.A.6 Zoning acknowledges that there is a building expansion calculation on the plan. Based on the last approved site plan the central area now being used for vehicle parking constitutes a lot area expansion. Provide a lot area expansion calculation on the plan.

15. Ensure that all changes to the site plan are reflected on the landscape plan.

16. Additional comments may be forth coming depending on how each comment has been addressed.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956.

C:\planning\site\t07cm01873.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised site plan and additional requested documents
06/04/2007 STEVE SHIELDS ZONING HC SITE REVIEW Denied See Zoning Comments
06/04/2007 SSHIELD1 ADA REVIEW Passed
06/06/2007 PETER MCLAUGHLIN LANDSCAPE REVIEW Denied Provide a copy of the last approved landscape plan with the resubmittal of the site plan.
06/06/2007 PETER MCLAUGHLIN NPPO REVIEW Passed
07/05/2007 LOREN MAKUS ENGINEERING REVIEW Denied July 5, 2007
T07CM01873
Site Plan Review

The Site Plan cannot be approved at this time. Address the following comments and submit a revised site plan for review. Include a letter that details how each comment has been addressed.

1. Revise the sight visibility triangles to meet the curb at the end of the triangle.
2. Include a statement indicating the cut and fill quantities for all earthwork that will be required to complete this project.
3. Provide a legend for the symbols used on the site plan. There are several areas where the shading greatly reduces the clarity of the plan. Consider removing or significantly lightening the shading to improve legibility.
4. Show the sight visibility triangle for the southern entry gate.
5. Please do a quality control check on the plans. Make sure that the arrows and labels indicate the correct plan features.
6. Provide a copy of the previously approved site plan and drainage report. The site plan must be consistent with the previously approved drainage report or a new drainage report addressing this proposal must be provided.

If you have any questions or wish to set up a meeting, I can be reached at 520.837.4927 or loren.makus@tucsonaz.gov.

Loren Makus, EIT
Senior Engineering Associate

Final Status

Task End Date Reviewer's Name Type of Review Description
07/09/2007 SUE REEVES OUT TO CUSTOMER Completed