Permit Number: T07CM01841
Parcel: 12702278B

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T07CM01841
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/02/2007 TERRY STEVENS ZONING REVIEW Approved
05/02/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Show that the common ventilation for the spaces comply with Section 403.3.2, IMC 2003.
2. Indicate the location of the thermostats for the three roof top units.
3. Show the termination points for the condensate drains for the roof top units.
05/02/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
05/02/2007 ROBERT SHERRY WATER REVIEW Approved
05/02/2007 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Approved
05/02/2007 GBONILL1 WWM REVIEW Needs Review
05/02/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide the required drinking fountain.
05/02/2007 JASON GREEN ENGINEERING REVIEW Approved
05/02/2007 MARTIN BROWN FIRE REVIEW Approved
05/02/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review