Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T07CM01837
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/02/2007 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 05/02/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide calculations showing that there is adequate ventilation for the space. Reference Section 402, IMC 2003. 2. Clarify the nature of the coil and furnace shown on sheet E1.0. Reference Section 106.3.1, IMC 2003. |