Review Details: COMMERCIAL TI
Permit Number - T07CM01792
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
04/30/2007 | TERRY STEVENS | ZONING | REVIEW | Approved | |
04/30/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide calculations demonstrating adequate ventilation. Reference Section 401.2, IMC 2003. 2. The design appears to be for a return air plenum. If so, add a note specifying that all materials exposed in the plenum shall conform to Section 602.2.1, IMC 2003. |
04/30/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T07CM01792 4/30/07 1. Water Heater rated for 230/1/3600W on Sheet P1. Electrical provides 120/1/3000W. Coordinate with Plumbing and clarify. |
04/30/2007 | ROBERT SHERRY | WATER | REVIEW | Approved | |
04/30/2007 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Approved | |
04/30/2007 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
04/30/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Clarify the riser diagram so that the waste piping is not shown connected to the water heater. |
04/30/2007 | DAVE MANN | FIRE | REVIEW | Approved | |
04/30/2007 | JOHN WILLIAMS | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
05/08/2007 | DROBEY1 | WWM | REVIEW | Needs Review |