Permit Number: T07CM01792
Parcel: 10821328B

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T07CM01792
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/30/2007 TERRY STEVENS ZONING REVIEW Approved
04/30/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide calculations demonstrating adequate ventilation. Reference Section 401.2, IMC 2003.
2. The design appears to be for a return air plenum. If so, add a note specifying that all materials exposed in the plenum shall conform to Section 602.2.1, IMC 2003.
04/30/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T07CM01792 4/30/07

1. Water Heater rated for 230/1/3600W on Sheet P1. Electrical provides 120/1/3000W. Coordinate with Plumbing and clarify.
04/30/2007 ROBERT SHERRY WATER REVIEW Approved
04/30/2007 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Approved
04/30/2007 LOREN MAKUS ENGINEERING REVIEW Approved
04/30/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Clarify the riser diagram so that the waste piping is not shown connected to the water heater.
04/30/2007 DAVE MANN FIRE REVIEW Approved
04/30/2007 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
05/08/2007 DROBEY1 WWM REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
05/08/2007 DELMA ROBEY APPROVAL SHELF Completed
05/08/2007 DELMA ROBEY OUT TO CUSTOMER Completed
05/08/2007 DELMA ROBEY REJECT SHELF Completed