Review Date Reviewer's Name Type of Review Description Status Comments
04/30/2007 DAVE MANN FIRE REVIEW Approved
04/30/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
04/30/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T07CM01790 4/30/07

1. Provide power requirements for electric door strike.
2. Provide electrical circuits for electric door strike and all new receptacles.
3. Provide panel schedule with load calculations.
04/30/2007 ROBERT SHERRY WATER REVIEW Approved
04/30/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
04/30/2007 RSHERRY1 WWM REVIEW Passed
08/29/2007 GBONILL1 BUILDING-COMMERCIAL REVIEW Needs Review
08/29/2007 GBONILL1 ENGINEERING REVIEW Needs Review
08/29/2007 GBONILL1 ZONING REVIEW Needs Review
08/29/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
08/29/2007 GERARDO BONILLA OUT TO CUSTOMER Completed