Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T07CM01765
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
04/26/2007 | HEATHER THRALL | ZONING | REVIEW | Approved | |
04/26/2007 | PATRICIA GILBERT | ENGINEERING | REVIEW | Approved | |
04/27/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference Section 302.3, Uniform Administrative Code, 1997. 2. Provide water isometrics and waste and vent isometrics for the new work. Reference Section 103.2.3, UPC 2003. 3. Provide a natural gas piping design, including the piping layout on a floor plan, the sizes, loads and developed lengths of the piping. Reference Section 103.2.3, UPC 2003. |
04/27/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference Section 302.3, Uniform Administrative Code, 1997. 2. Condensate drains may not terminate directly to the roof. Provide the size, route, and termination of the condensate drain. Reference Section 307.2.1, IMC 2003, as amended by the City of Tucson. 3. Show that the trap for the condensate is being installed in accordance with the manufacturer's installation requirements. Reference Section 304.1, IMC 2003. 4. Provide calculations demonstrating adequate ventilation. Reference Section 401.2, IMC 2003. 5. Clarify the status of EF-1; is it new or existing? |
04/27/2007 | JWILLIA5 | BUILDING-COMMERCIAL | REVIEW | Approved | |
04/27/2007 | ROBERT SHERRY | WATER | REVIEW | Approved | |
05/01/2007 | MARTIN BROWN | FIRE | REVIEW | Approved | |
05/07/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T07CM01765 5/3/07 1. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference Section 302.3, Uniform Administrative Code, 1997. 2. Clarify the status of EF-1; is it new or existing? 3. Feeder to replacement AC, 2 sets of 300 KCMIL, may allow an excessive amount of fault current to the new unit. Provide Available fault calculations and fault current rating of new AC terminals. Suggest the use of current-limiting overcurrent protective device. Per conversation with Hub Phipps, 5/7/07, this feeder supplies an existing panel, Panel AC, and the replacement air conditioning unit is on an existing 30A branch circuit to Panel AC, with #10 conductor. Comment is satisfied with this explanation. |
05/11/2007 | CAGUILA1 | WWM | REVIEW | Needs Review | |
05/11/2007 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |