Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T07CM01756
Parcel: 11917013D

Review Status: Completed

Review Details: POST 3RD PARTY REVIEW

Permit Number - T07CM01756
Review Name: POST 3RD PARTY REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/13/2007 ROBERT SHERRY WATER REVIEW Denied 1. Provide backflow protection to isolate the irrigation system from the building water supply. Reference Section 603.4.6.1, UPC 2003.
2. Reduced pressure backflow prevention assemblies shall have a diameter at least equal to the diameter of the service connection or the service line at the point of connection. Reference Section 27-76 (b), COT Ordinance 9976, http://www.tucsonaz.gov/water/docs/backflow-ord.pdf
06/13/2007 DAVE MANN FIRE REVIEW Approved
06/15/2007 SREEVES1 ENGINEERING REVIEW Needs Review
06/15/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
06/15/2007 SREEVES1 ZONING REVIEW Needs Review
06/15/2007 SREEVES1 WWM REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
06/15/2007 SUE REEVES OUT TO CUSTOMER Completed