Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 3RD
Permit Number - T07CM01718
Review Name: REVISION - - 3RD
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/06/2008 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL. PLEASE CALL AT 520.837.4907 OR EMAIL AT Linda.Buczynski@tucsonaz.gov IF YOU CARE TO DISCUSS. 1. Previous Sheet E-1 was approved on Revision 1 dated 3/27/08 and approved 3/31/08. Indicate date and nature of current revision. 2. Reinstate Lighting Fixture Schedule on the plans. 3. Provide overcurrent protection for the feeder between the new service disconnect and the gutter. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 06/09/2008 | CINDY AGUILAR | APPROVAL SHELF | Completed |
| 06/09/2008 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |