Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T07CM01715
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/07/2007 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Denied | 1) PROVIDE STRUCTURAL CALCUALTIONS JUSTIFYING CONNECTORS AND METAL STUD WALL CAN CARRY THE 700 LB. WATER HEATER LOAD. 2) JUSTIFY OCCUPANCY PER TABLE 1004.1.2 LOBBY / STANDING ARE = 1/5, SEATING IS 1/15 IT APPEARS TWO RESTROOMS ARE REQUIRED. |
| 05/21/2007 | GBONILL1 | MECHANICAL-COMMERCIAL | REVIEW | Needs Review | |
| 05/21/2007 | GBONILL1 | PLUMBING-COMMERCIAL | REVIEW | Needs Review |