Permit Number: T07CM01715
Parcel: 10321342A

Address:
2112 W GRANT RD

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T07CM01715
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/03/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
05/07/2007 EGRANT1 MECHANICAL-COMMERCIAL REVIEW Denied Show how the ventilation of the area complies with the requirements of Section 403.3, IMC 2003.
05/07/2007 EGRANT1 PLUMBING-COMMERCIAL REVIEW Denied 1. Appliances (e.g. water filter, espresso machine) to be directly connected to the water supply system that do not have listed, integral backflow preventers or integral air gaps require backflow preventers. Specify the backflow prevention method to be used. Reference Section 603.0, UPC 2003.
2. Provide an upper terminal cleanout for the floor sink in the western end of the space. Reference Section 707.4, UPC 2003.
3. Provide material standards for all plumbing fixtures shown as "model to be determined". Reference Section 401.1, UPC 2003.