Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T07CM01715
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/03/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 05/07/2007 | EGRANT1 | MECHANICAL-COMMERCIAL | REVIEW | Denied | Show how the ventilation of the area complies with the requirements of Section 403.3, IMC 2003. |
| 05/07/2007 | EGRANT1 | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Appliances (e.g. water filter, espresso machine) to be directly connected to the water supply system that do not have listed, integral backflow preventers or integral air gaps require backflow preventers. Specify the backflow prevention method to be used. Reference Section 603.0, UPC 2003. 2. Provide an upper terminal cleanout for the floor sink in the western end of the space. Reference Section 707.4, UPC 2003. 3. Provide material standards for all plumbing fixtures shown as "model to be determined". Reference Section 401.1, UPC 2003. |