Permit Number: T07CM01715
Parcel: 10321342A

Address:
2112 W GRANT RD

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T07CM01715
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/26/2007 STEVE SHIELDS ZONING REVIEW Approved
04/26/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Needs Review
04/26/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied t07cm01715 4/26/07

1. Water heater takes 240V power according to Plumbing Fixture Schedule. Electrical provides 208V. Coordinate with Mechanical and clarify.
2. Ckt 2 supplies Lighting + EF according to the description on the Panel Schedule. Load only accounts for the lighting. Please clarify.
04/26/2007 ROBERT SHERRY WATER REVIEW Approved
04/26/2007 ROBERT SHERRY BUILDING-COMMERCIAL REVIEW Approved
04/26/2007 ANY ENGINEERING REVIEW Approved
04/26/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Needs Review
04/26/2007 DAVE MANN FIRE REVIEW Approved
04/26/2007 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
05/03/2007 GERRY KOZIOL WWM REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
05/03/2007 GERARDO BONILLA OUT TO CUSTOMER Completed