Permit Review Detail
Review Status: Completed
Review Details: POST 3RD PARTY REVIEW
Permit Number - T07CM01713
Review Name: POST 3RD PARTY REVIEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/02/2007 | JOHN WILLIAMS | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 08/03/2007 | MARTIN BROWN | FIRE | REVIEW | Approv-Cond | Please see notes on Sheet g0.1. Hazard classification notes on sheet p2.1 are incorrect. Verify total area served by a single fire riser does not exceed 52,000 sq. ft. |
| 08/08/2007 | ROBERT SHERRY | WATER | REVIEW | Denied | 1. Clarify the relationship of the calculations shown on sheet P2.1 with the water piping shown on sheet P1.0 and the existing water meter and backflow preventer. 2. Provide a letter from Tucson Water confirming that the use of the existing 2" water meter serving the auditorium will be allowed for this project. |
| 08/09/2007 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 08/13/2007 | TERRY STEVENS | ZONING | REVIEW | Passed | |
| 08/21/2007 | PATRICIA GILBERT | ENGINEERING | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/22/2007 | CINDY AGUILAR | APPROVAL SHELF | Completed |
| 08/22/2007 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |