Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL BLDG/ZONING/ENGINE/NPPO
Permit Number - T07CM01693
Review Name: RESIDENTIAL BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/24/2007 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 05/24/2007 | JASON GREEN | ENGINEERING | REVIEW | Approved | Proposed construction is located outside of the SFHA. |
| 05/24/2007 | MICHAEL ST. PAUL | NPPO | REVIEW | Passed | |
| 05/24/2007 | DAVE WITT | BUILDING-RESIDENTIAL | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 06/08/2007 | DELMA ROBEY | APPROVAL SHELF | Completed |
| 06/08/2007 | DELMA ROBEY | OUT TO CUSTOMER | Completed |
| 06/08/2007 | DELMA ROBEY | REJECT SHELF | Completed |