Review Date Reviewer's Name Type of Review Description Status Comments
05/29/2007 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS
Activity # T07CM01679
Date: 5/29/07

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2003 International Residential Code, 2003 International Energy Conservation Code, and Arizona State amendments to the 2003 Uniform Plumbing Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:
All corrections and revisions shall be made on original tracings or finished reproducible set. Return this set and a copy along with a set of the first submission. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets.

As of 9-02-04 the City of Tucson has adopted the 2003 IRC with the exception of the plumbing portion which has been replaced with the 2003 UPC with amendments. All plans should reference these codes.

I. SITE PLAN:
1. Add plumbing reference to index

II. FLOOR PLAN:
1. Verify proposed window size over kitchen counter.
2. Specify window size at intersecting 6" patio wall.
3. Provide tempered glass within 24" of doorways, R308.4.
4. Specify proposed use of existing kitchen space. Will existing counters, sink, and refrigerator be removed?

III. ROOF PLAN:
1. Cross-reference or remove keynotes 7-15 on page 4.
2. Specify lumber grade and species, R802.1.
3. Specify size and spacing of pre-engineered trusses.
4. Provide manufacturer's calculations and data for pre-engineered trusses dated and wet-sealed by an engineer who is registered in Arizona, or note the requirement for deferred submittal. Truss calculations shall be cross-referenced to the floor plans, R802.10.2.
5. Provide an attic space calculation and specify size and location of all vents needed to comply, R806.2.

IV. SECTIONS - DETAILS:
1. Provide accurate cross-references between sections and details.
2. Note and specify a complete roofing system: Roofing type, grade of materials and method of installation, R905.
3. Specify roof sheathing and method of attachment.
4. Show the ceiling gypsum board as either 5/8" or ½" sag resistant when applied to 24" o/c framing, Table R702.3.5 footnote d.
5. Provide joint reinforcement and bond beams within masonry walls, R606.10.
6. Provide treated sill plates bearing on concrete slabs, R319.1.

V. PLUMBING PLAN:
1. The City of Tucson has adopted the 2003 Uniform Plumbing Code with state amendments (ARIZONA STATE PLUMBING CODE). The plans should reference this code, or appeal to the Building Official for IRC design approval.
2. Clarify piping materials used, plumbing notes on page 6 do not agree with notes on page 7.
3. Provide a note for underground facility tracer wires per DSD Memo, 10/24/2005.
4. Provide a fixture unit schedule (to include existing fixtures) per 2003 UPC Tables 6-4 and 7-3.
5. Provide water pressure range, maximum developed length, and diameter of water line from the meter, UPC Table 6-5.
6. Show a clean out at the kitchen sink area UPC 707.4 W/ State amendment.
7. Provide a gas line isometric and size the supply pipe for the connected demand. Include the BTU demand and length of line to each gas appliance, size and length of each branch, and the total demand and total developed length from the meter to the most remote appliance on the system. UPC 1217.0, 1217.2, & Table 12-7.

VI. MECHANICAL PLAN:
1. Remove mechanical notes that do not apply

VII. ELECTRICAL PLAN:
1. The City of Tucson has adopted the 2003 IRC with amendments. The plans should reference this code, or appeal to the Building Official for 2006 IRC design approval.
2. Provide electrical load calculations for existing house and proposed circuits, E3502.2.
3. Provide the nameplate rating or a dedicated circuit for the proposed baseboard heater.
4. Show receptacle outlets at kitchen counter spaces so that no point along the wall line is more than 24" from a receptacle outlet, E3801.4.1.

VIII. OUTDOOR LIGHTING CODE:
1. Show compliance with City of Tucson Outdoor Lighting Code with an approved lighting calculation in accordance with OLC 3.1.2. Include all exterior fixtures on the property in the calculations.
2. Provide cut sheets for all full cut-off fixtures showing the angle of cutoff, light emissions and fixture wattage. All other fixtures are assumed to be unshielded (non-FCO style).

IX. INTERNATIONAL ENERGY CONSERVATION CODE:
1. Show the proposed "U" factors of the windows and doors on the plan.

V. DETACHED GARAGE:
1. Note and specify the ICBO evaluation report number, system name and manufacturer with the vapor barrier for thin-coat stucco systems over foam board, R703.6.
2. Show the ceiling gypsum board as either 5/8" or ½" sag resistant when applied to 24" o/c framing, IRC table R702.3.5 footnote d.
3. Specify roof sheathing and method of attachment.
4. All exterior wall lines shall be braced. Provide a complete braced wall layout, R602.10.

If you have any questions please contact:
Clayton Trevillyan
(520) 837-4913
City of Tucson Residential Plan Review