Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T07CM01666
Review Name: REVISION - - 1ST
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/23/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 07/24/2008 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 07/24/2008 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | 501 W Grant Rd T07CM01666 One item remains to be cleared, one 60 amp circuit feeds 5 --240 volt receptacles,each receptacle being fed with #6 awg conductors. Two things may occur, 1. the five receptacles being used at once to feed coffee machines would overload the one circuit , 2. the one 60 amp circuit would be too large to protect individual coffee machines. You do not provide reference for the coffee machines, however in reviewing past situations like this each unit is on it's own circuit with it's own overcurrent protection. Review with provider of coffee machines and provide exalty what is required. Ray T Majuta DSD City of Tucson Electrical Plan Check 520-8374988 7/28/08 |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 07/29/2008 | DELMA ROBEY | OUT TO CUSTOMER | Completed |
| 07/29/2008 | DELMA ROBEY | REJECT SHELF | Completed |