Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T07CM01666
Review Name: REVISION - - 1ST
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/08/2008 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | The following items need to be corrected---- 1. The light fixture schedule shows A and C to be 277volt, this is a 120/240v system. 2. Sheet E-1 does not show the heating and colling equipment. 3. The Electrical plan shows several 220 volt receptacles on circuit 6 which only a 120 v circuit. 4. The flood lights on the exterior are not circuited, nor on the exterior light load calculations. 5. Circuit 24 is shown on panel schedule for exterior receptacles however a kitchen receptacle is on there. 6. Circuit 8 is not on the plan. 7. landscape lights not shown. 8. Circuit 24 on panel schedule shows exterior recptacles, none on plan. Ray T Majuta DSD Plan Check 520-8374988 7/09/08 |
| 07/08/2008 | DAVE MANN | FIRE | REVIEW | Approved | |
| 07/10/2008 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | PARAPET EXTENSION AND ROOF DRAINAGE CHANGES ARE NOT SHOWN ON DRAWINGS. PROVIDE 3/4" SCALE WALL SECTION SHOWING PARAPET EXTENSION AND A ROOF PLAN SHOWING ROOF CHANGES AND DRAINAGE CORRECTIONS. |
| 07/18/2008 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 07/18/2008 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Clarify the duct insulation |
| 07/18/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Revise waste & vent schematic tocoordinate with the plumbing plan. 2. Provide a drinking fountain. 3. Clarify the specifications of the new sinks. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 07/18/2008 | CINDY AGUILAR | APPROVAL SHELF | Completed |
| 07/18/2008 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |