Permit Number: T07CM01666
Parcel: 115150510

Address:
501 W GRANT RD

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T07CM01666
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/08/2008 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied The following items need to be corrected----

1. The light fixture schedule shows A and C to be 277volt,
this is a 120/240v system.
2. Sheet E-1 does not show the heating and colling equipment.
3. The Electrical plan shows several 220 volt receptacles on
circuit 6 which only a 120 v circuit.
4. The flood lights on the exterior are not circuited, nor on the exterior light load calculations.
5. Circuit 24 is shown on panel schedule for exterior receptacles however a kitchen receptacle is on there.
6. Circuit 8 is not on the plan.
7. landscape lights not shown.
8. Circuit 24 on panel schedule shows exterior recptacles,
none on plan.


Ray T Majuta
DSD Plan Check
520-8374988
7/09/08
07/08/2008 DAVE MANN FIRE REVIEW Approved
07/10/2008 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied PARAPET EXTENSION AND ROOF DRAINAGE CHANGES ARE NOT SHOWN ON DRAWINGS. PROVIDE 3/4" SCALE WALL SECTION SHOWING PARAPET EXTENSION AND A ROOF PLAN SHOWING ROOF CHANGES AND DRAINAGE CORRECTIONS.
07/18/2008 GERRY KOZIOL WWM REVIEW Approved
07/18/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Clarify the duct insulation
07/18/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise waste & vent schematic tocoordinate with the plumbing plan.
2. Provide a drinking fountain.
3. Clarify the specifications of the new sinks.

Final Status

Task End Date Reviewer's Name Type of Review Description
07/18/2008 CINDY AGUILAR APPROVAL SHELF Completed
07/18/2008 CINDY AGUILAR OUT TO CUSTOMER Completed