Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T07CM01666
Parcel: 115150510

Address:
501 W GRANT RD

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T07CM01666
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/17/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Comment not addressed (fourth request). Provide the listing for the two-way cleanout fitting called out on the plumbing plan, sheet P-1. Reference Sections 103.2.3 and 707.6, UPC 2003. (Note that a 2-way cleanout is not required per Section 707.4 unless an upper terminal cleanout is not installed but if used, the 2-way cleanout shall be a listed fitting.)
2. The rim elevation of the next upstream sanitary manhole (2350.8) is higher than the first floor elevation (2349.8). Provide a backwater valve per Section 710.1, UPC 2003, as amended by the City of Tucson with cleanouts per Section 707.4 and venting per Section 904.1, UPC 2003.
3. Clarify the size of the building sewer; it is shown as 4" on the site plan and 3" on sheet P-1. If the building sewer is actually 3", it shall have a minimum slope of 1/4" per foot (General Note #10, P-1). Reference: Sections 103.2.3, 708.0, and 718.1, UPC 2003.
03/17/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Comment not addressed. Provide the installed weight of the rooftop equipment (i.e. provide the manufacturer, model, and weight of the unit that was used as the basis for the design) Reference: Section 106.3.1, IMC 2003.
2. Show the location, design, and attachment details for the proposed maintenance guards. Reference: Section 304.10, IMC 2003.
03/18/2008 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied CLARIFY ROOF MOUNTED MECHANICAL UNIT STEEL FRAME ATTACHMENT THROUGH CLAY TILE TO STRUCTURE AND MAINTENANCE ACCESS TO UNIT