Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T07CM01666
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
03/17/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Comment not addressed (fourth request). Provide the listing for the two-way cleanout fitting called out on the plumbing plan, sheet P-1. Reference Sections 103.2.3 and 707.6, UPC 2003. (Note that a 2-way cleanout is not required per Section 707.4 unless an upper terminal cleanout is not installed but if used, the 2-way cleanout shall be a listed fitting.) 2. The rim elevation of the next upstream sanitary manhole (2350.8) is higher than the first floor elevation (2349.8). Provide a backwater valve per Section 710.1, UPC 2003, as amended by the City of Tucson with cleanouts per Section 707.4 and venting per Section 904.1, UPC 2003. 3. Clarify the size of the building sewer; it is shown as 4" on the site plan and 3" on sheet P-1. If the building sewer is actually 3", it shall have a minimum slope of 1/4" per foot (General Note #10, P-1). Reference: Sections 103.2.3, 708.0, and 718.1, UPC 2003. |
03/17/2008 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Comment not addressed. Provide the installed weight of the rooftop equipment (i.e. provide the manufacturer, model, and weight of the unit that was used as the basis for the design) Reference: Section 106.3.1, IMC 2003. 2. Show the location, design, and attachment details for the proposed maintenance guards. Reference: Section 304.10, IMC 2003. |
03/18/2008 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | CLARIFY ROOF MOUNTED MECHANICAL UNIT STEEL FRAME ATTACHMENT THROUGH CLAY TILE TO STRUCTURE AND MAINTENANCE ACCESS TO UNIT |