Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T07CM01666
Parcel: 115150510

Address:
501 W GRANT RD

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T07CM01666
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/06/2008 STEVE SHIELDS ZONING REVIEW Approved
02/07/2008 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
02/11/2008 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
02/14/2008 GERRY KOZIOL WWM REVIEW Approved
03/05/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide the installed weight of the rooftop equipment. Reference: Section 106.3.1, IMC 2003.
2. Show how HP-1 is to be mounted on the tile roof. Reference: Section 106.3.1, IMC 2003.
3. Provide structural calculations to verify that the existing roof is capable of supporting the additional dead load due to the installation of the roof top units. Reference: Section 302.1, IMC 2003.
4. Provide guards for equipment located within 10 feet of a roof edge or of a walking surface that is elevated more than 30 inches above the adjoining grade. Reference: Section 304.10, IMC 2003.
03/05/2008 ROBERT SHERRY WATER REVIEW Approved
03/05/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Comment not addressed (third request). Provide the listing for the two-way cleanout fitting called out on the plumbing plan, sheet P-1. Reference Sections 103.2.3 and 707.6, UPC 2003. (Note that a 2-way cleanout is not required per Section 707.4 unless an upper terminal cleanout is not installed but if used, the 2-way cleanout shall be a listed fitting.)

Final Status

Task End Date Reviewer's Name Type of Review Description
03/12/2008 CPIERCE1 OUT TO CUSTOMER Completed
03/12/2008 SHANAE POWELL REJECT SHELF Completed