Permit Number - T07CM01633
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/24/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T07CM01633 4/24/07 1. Receptacles shall be counted at no less than 180VA per outlet. Reference NEC 220.3 (B) (9). For example, Ckt 2 has 8 receptacles for a total of 1440VA, not 720. Typical for all circuits for which this applies. 2. Ckt 1, with 6 pendant fixtures, would have (6) (150) = 900VA for those fixtures alone. The 2 X 4 fluorescent fixtures on the same circuit shall be added to this total, and the power requirements of such fixtures need to be defined on the plans to allow the Examiner to continue review. Typical for all circuits for which this applies. 3. Provide a Lighting Fixture Schedule on the plans. Could not find a recessed fixture in cut sheets. Label which fixture is which on the cut sheets. |
| 04/26/2007 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review | |
| 04/26/2007 | DROBEY1 | BUILDING-COMMERCIAL | REVIEW | Denied |