Review Details: RESIDENTIAL BLDG/WWM

Permit Number - T07CM01632
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/07/2007 GERRY KOZIOL WWM REVIEW Approved
05/14/2007 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS
Activity # T07CM01632
Date: 5/16/07

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2003 International Residential Code, 2003 International Energy Conservation Code, and Arizona State amendments to the 2003 Uniform Plumbing Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:
All corrections and revisions shall be made on original tracings or finished reproducible set. Return this set and a copy along with a set of the first submission. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets.

I. SITE PLAN:
1. Provide a note for underground facility tracer wires per DSD Memo, 10/24/2005.

II. FLOOR PLAN:
1. Provide fire rated assembly for attic access in garage, or specify separation of attic space between house and garage, R309.2.
2. Specify length of 4-foot tall section of kitchen wall.

III. STRUCTURAL PLAN:
1. Provide calculations to justify size of porch beam at rear of house.
2. Truss calculations must be signed, dated and wet-sealed by an engineer who is registered in Arizona. Truss calculations shall be cross-referenced to the floor plans. The engineer of record shall review and stamp the truss shop drawings or note the requirement for deferred submittal.

IV. ELEVATIONS:
1. Specify attic protection from rigid foam on gable ends, R314.2.3.

V. SECTIONS - DETAILS:
1. Provide detail for top-plate reinforcement at 6x12 porch beam around corner of exterior, R602.3.2.
2. Provide detail for bracing trusses at gable ends to prevent rotation and provide lateral stability, R802.10.3.
3. Provide detail for location and methods of flashing wall-to-roof intersections, R903.2.1.
4. Specify method of transferring lateral forces from the roof diaphragm to the supporting structural elements, 801.2.
5. Show a minimum 1" ventilation clearance between ceiling insulation and roof sheathing if insulation is attached to truss bottom cords and eave venting is used, R806.3.

VI. PLUMBING PLAN:
1. The City of Tucson has adopted the 2003 Uniform Plumbing Code with state amendments (ARIZONA STATE PLUMBING CODE). The plans should reference this code only, or appeal to the Building Official for IRC design approval.
2. Provide the maximum developed length of water line from the meter to the furthest fixture served, UPC 610.1.
3. Each dwelling unit requires an individual accessible water supply shut off, UPC 605.3.
4. Show a clean out at the kitchen sink area UPC 707.4 W/ State amendment.
5. Provide gas piping for structure or submit exemption documentation, Arizona Statute 30-809

VII. MECHANICAL PLAN:
1. Show dryer vent location for venting to exterior, M1501.
2. Provide an equipment specification list including the make and model numbers for all equipment, M1401.3.
3. Provide location of condensate drain line and disposal from HVAC unit, M1411.3.
4. Provide the nominal size of return air register, M1602.

VIII. ELECTRICAL PLAN:
1. Provide circuit number references next to HP-01 on electrical plan.

IX. OUTDOOR LIGHTING CODE:
1. Provide cut sheets for all FCO fixtures showing the angle of cutoff, light emissions and fixture wattage. All other fixtures are assumed to be unshielded (non-FCO style).

If you have any questions please contact:
Clayton Trevillyan
(520) 837-4913
City of Tucson Residential Plan Review