Permit Number: T07CM01613
Parcel: 125030850

Address:
2914 E 4TH ST

Review Status: Completed

Review Details: RESIDENTIAL BLDG/WWM

Permit Number - T07CM01613
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/27/2007 GERRY KOZIOL WWM REVIEW Approved
06/06/2007 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS
Activity # T07CM01613
Date: 6/08/07

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2003 International Residential Code, 2003 International Energy Conservation Code, and Arizona State amendments to the 2003 Uniform Plumbing Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

I. GENERAL REQUIREMENTS:
1. An architect or an engineer usually prepares construction drawings for commercial projects; however, these services are also available to homeowners. Contractors may also be a useful resource when preparing construction drawings. Regardless of who prepares these documents, all drawings must be detailed, accurate, neat, and complete (no pencil). Construction drawing guidelines are available from the residential desk of the Development Services Division.
2. Provide new drawings at the proper scale (min. ¼" = 1') on pages that do not contain prior approval stamps.
3. As of 9-02-04 the City of Tucson has adopted the 2003 IRC with the exception of the plumbing portion which has been replaced with the 2003 UPC with amendments. All plans should reference these codes.
4. Provide a note for underground facility tracer wires per DSD Memo, 10/24/2005.

II. FOUNDATION:
1. Specify all anchor-bolt embedment minimum 7" into concrete or masonry, R403.1.6.
2. Show the minimum 12" footing depth below undisturbed soil, R403.1.4.

III. FLOOR PLAN:
1. Label all rooms and spaces (porch?). Show all doors and windows.
2. Provide all window and door sizes and types.
3. Show compliance with R310 providing egress from bedrooms (new bedrooms and existing bedrooms that adjoin new rooms) to meet the following minimum specifications.
· Maximum sill height of 44".
· Minimum net clear opening area of 5.7sqft (5 sq.ft 2nd floor).
· Minimum net clear opening dimension of 24" height and 20" width.

IV. STRUCTURAL PLAN:
1. Specify lumber grade and species, R802.1.
2. Specify size of all headers in exterior, and interior bearing, walls.
3. Specify length of roof overhang.
4. Clarify roof detail that shows a dropped ceiling. Specify size and spacing of dropped ceiling materials.
5. Specify supporting members for roof structure over porch area.

V. ELEVATIONS:
1. Note and specify the ICBO evaluation report number, system name and manufacturer with the vapor barrier for thin-coat stucco systems over foam board, R703.6.
2. Note and specify all roof slopes appropriate with selected material, R901.1. (Minimum allowable slope for Built-up roof is ¼" per foot, R905.9.1. Minimum allowable slope for Roll roofing is 1" per foot, R905.5.2.)
3. Note and specify a complete roofing system: Roofing type, grade of materials and method of installation, R905.

VI. PLUMBING PLAN:
1. Note and specify all piping materials, UPC 301.1.1.
2. Provide water pressure range, maximum developed length, and diameter of water line from the meter allowing for pressure difference in elevation between such source of supply and highest water supply outlet, UPC 640.8, Table 6-5.
3. Provide a fixture unit schedule (to include existing fixtures) per 2003 UPC Tables 6-4 and 7-3.
4. Note on plan compliance with the water conservation requirements. Water closets, 1.6 gallons per flush, sinks and showerheads, 3 gallons per minute, State Amend. R4-48-104.
5. Note on plans that shower and tub / shower combinations that have individual control valves shall be of the pressure balance or thermostatic mixing valve type.
6. Note that tub/shower enclosures shall have nonabsorbent surfaces to 6' above the floor, R307.2. All glass enclosures shall be tempered, R308.4.5.
7. Provide location and method of installation for water supply tie-in.

VII. MECHANICAL PLAN:
1. Show bathroom exhaust fan locations for venting to exterior with minimum 50 CFM rating R303.3 and M1506.
2. Provide return air from proposed addition, M1602.

VIII. ELECTRICAL PLAN:
1. Show locations of smoke detectors, R313. Note that all smoke detectors must be interconnected with a power source from the building wiring, and shall be equipped with battery backup. When ceiling finish materials are removed in existing construction, existing bedrooms shall be in compliance. When ceiling finish materials are not removed, existing bedrooms shall be equipped with battery operated smoke detectors, R313.1.1.
2. Note that an arc-fault circuit interrupter shall protect bedroom outlets including receptacles, lights and smoke detectors, E3802.11.

IX. OUTDOOR LIGHTING CODE:
1. Show compliance with City of Tucson Outdoor Lighting Code with an approved lighting calculation in accordance with OLC 3.1.2. Include all exterior fixtures on the property in the calculations.
2. Provide cut sheets for all full cut-off fixtures showing the angle of cutoff, light emissions and fixture wattage. All other fixtures are assumed to be unshielded (non-FCO style).

If you have any questions please contact:
Clayton Trevillyan
(520) 837-4913
City of Tucson Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
06/11/2007 THAUSER1 OUT TO CUSTOMER Completed
06/11/2007 THAUSER1 REJECT SHELF Completed