Permit Number: T07CM01522
Parcel: 128030110

Review Status: Completed

Review Details: PLANS OK TO SUBMIT - 3RD PARTY

Permit Number - T07CM01522
Review Name: PLANS OK TO SUBMIT - 3RD PARTY
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/12/2007 TERRY STEVENS ZONING REVIEW Needs Review
04/12/2007 JWILLIA5 BUILDING-COMMERCIAL REVIEW Needs Review
04/12/2007 LOREN MAKUS ENGINEERING REVIEW Needs Review
04/16/2007 DAVE MANN FIRE REVIEW Denied Sheet G3.00

1. Show smoke evacuation system or calculations for passive smoke for J.C. Penny court. It scales as narrower than court previously calculated for cross court egress. Also see Sheet AS1.00.

2. Show the location and clearance of the hydrants, water lines, and fire department connections in the area of the addition and remodel. There are several at the Northwest corner of the new garage.

3. This sheet shows 60 feet north and 40 feet east of the garage as clear space. Sheet 3.01 shows 40 feet north and 60 feet to the east. Please clarify and note that if either dimension is less than 60 feet the parking garage needs to be fire sprinklered or comply with IBC Sections 3104 and 406.

Sheet FP 5.01 Shopping malls and storage areas are required to be of an Ordinary II hazard classification.

Final Status

Task End Date Reviewer's Name Type of Review Description
04/30/2007 GERARDO BONILLA OUT TO CUSTOMER Completed