Permit Review Detail
Review Status: Completed
Review Details: PLANS OK TO SUBMIT - 3RD PARTY
Permit Number - T07CM01522
Review Name: PLANS OK TO SUBMIT - 3RD PARTY
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/12/2007 | TERRY STEVENS | ZONING | REVIEW | Needs Review | |
| 04/12/2007 | JWILLIA5 | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
| 04/12/2007 | LOREN MAKUS | ENGINEERING | REVIEW | Needs Review | |
| 04/16/2007 | DAVE MANN | FIRE | REVIEW | Denied | Sheet G3.00 1. Show smoke evacuation system or calculations for passive smoke for J.C. Penny court. It scales as narrower than court previously calculated for cross court egress. Also see Sheet AS1.00. 2. Show the location and clearance of the hydrants, water lines, and fire department connections in the area of the addition and remodel. There are several at the Northwest corner of the new garage. 3. This sheet shows 60 feet north and 40 feet east of the garage as clear space. Sheet 3.01 shows 40 feet north and 60 feet to the east. Please clarify and note that if either dimension is less than 60 feet the parking garage needs to be fire sprinklered or comply with IBC Sections 3104 and 406. Sheet FP 5.01 Shopping malls and storage areas are required to be of an Ordinary II hazard classification. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 04/30/2007 | GERARDO BONILLA | OUT TO CUSTOMER | Completed |