Review Details: COMMERCIAL TI

Permit Number - T07CM01507
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/12/2007 MICHAEL ST. PAUL ZONING REVIEW Approved
04/12/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
04/12/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T07CM01507 4/12/07

(1981A) (1.25) = 2476 > 2000A. Load calculations will have to use a different methodology to demonstrate that service can accommodate new load. Reference NEC 220.35.