| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/12/2007 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 04/12/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
| 04/12/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T07CM01507 4/12/07 (1981A) (1.25) = 2476 > 2000A. Load calculations will have to use a different methodology to demonstrate that service can accommodate new load. Reference NEC 220.35. |