Permit Number: T07CM01497
Parcel: 124041020

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T07CM01497
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/20/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T07CM01497 4/20/07

1. Panel B-1 is listed on the Total Load Summary as "not used currently." B-1 is the new Panel, whose schedule is on Sheet E-2. Coordinate both sheets and clarify.
2. Add load of Panel B-1 to Total Load Summary.
3. There is a feeder to Panel H on the Riser Diagram, from a separate section from H1, H2, and H3. Please account for Panel H on the Total Load Summary.