Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T07CM01497
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/20/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T07CM01497 4/20/07 1. Panel B-1 is listed on the Total Load Summary as "not used currently." B-1 is the new Panel, whose schedule is on Sheet E-2. Coordinate both sheets and clarify. 2. Add load of Panel B-1 to Total Load Summary. 3. There is a feeder to Panel H on the Riser Diagram, from a separate section from H1, H2, and H3. Please account for Panel H on the Total Load Summary. |
| 05/01/2007 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |