Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T07CM01497
Parcel: 124041020

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T07CM01497
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/11/2007 STEVE SHIELDS ZONING REVIEW Approved
04/11/2007 LOREN MAKUS ENGINEERING REVIEW Approved
04/12/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T07CM01497 4/12/07

1. Electrical Plan and Total Load Summary show HP2 and HP3 on Panel A-2. Panel schedule with these units is B-1. Please clarify.
2. Account for Panels H and HP on Total Load Summary.
3. Account for Panels A1, A2, B2, H1, H2, H3, J and K on Riser Diagram.
4. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference Section 302.3, Uniform Administrative Code, 1997.
04/12/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
04/12/2007 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Passed
04/12/2007 ROBERT SHERRY WATER REVIEW Approved
04/12/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
04/12/2007 RSHERRY1 WWM REVIEW Passed
04/12/2007 MARTIN BROWN FIRE REVIEW Approved
04/20/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review