Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T07CM01497
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
04/11/2007 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
04/11/2007 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
04/12/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T07CM01497 4/12/07 1. Electrical Plan and Total Load Summary show HP2 and HP3 on Panel A-2. Panel schedule with these units is B-1. Please clarify. 2. Account for Panels H and HP on Total Load Summary. 3. Account for Panels A1, A2, B2, H1, H2, H3, J and K on Riser Diagram. 4. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference Section 302.3, Uniform Administrative Code, 1997. |
04/12/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
04/12/2007 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Passed | |
04/12/2007 | ROBERT SHERRY | WATER | REVIEW | Approved | |
04/12/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
04/12/2007 | RSHERRY1 | WWM | REVIEW | Passed | |
04/12/2007 | MARTIN BROWN | FIRE | REVIEW | Approved | |
04/20/2007 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |