Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T07CM01496
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/11/2007 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 04/11/2007 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 04/12/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T07CM01496 4/12/07 1. Provide panel and circuit for new lighting fixtures. 2. Provide panel and circuit for 50A, 208V receptacle. 3. Provide load description for 50A, 208V receptacle. 4. Provide load calculations for new electrical loads. 5. Provide conduit and conductor size for 50A, 208V receptacle. |
| 04/12/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference Section 302.3, Uniform Administrative Code, 1997. 2. Provide a Type I hood over the domestic oven/range being used for commercial purposes. Reference Section 507.2.3, IMC 2003. |
| 04/12/2007 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Denied | 1) PROVIDE BUDGET ON DRAWINGS JUSTIFYING 20% COST OF CONSTRUCTION BEING SPENT TOWARDS ACCESSIBILITY SECTION 3409.6 IBC 2003. 2) CLARIFY RECEPTION DESK HEIGHT. 3) CLARIFY WORK SURFACE HEIGHT IN BREAKROOM FOR SINK AND WORK SURFACE PER ANSI A117.1 2003 AND SECTION 804.3 AND SECTION 902. |
| 04/12/2007 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 04/12/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide plumbing plans for the new work, including existing plumbing floor plan for water and waste piping. Reference Section 103.2.3, UPC 2003. 2. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference Section 302.3, Uniform Administrative Code, 1997. |
| 04/12/2007 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 05/01/2007 | CAGUILA1 | WWM | REVIEW | Needs Review | |
| 05/01/2007 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |